PERIODIC INSPECTION & MAINTENANCE REQUIREMENTS FOR SPRINKLER SYSTEMS (AS AMENDED BY LOCAL LAW 10/99) 1 2 |
| Maintenance & Inspection | J-2 FOUR UNITS OR MORE | J-2 FOUR UNITS OR MORE (In a building 6 stories or 75 ft. in height or less with a secondary means of egress from all units and occupiable spaces) | J-2 THREE UNITS OR LESS | J-3 | ALL OTHER OCCUPANCIES
| must maintain in good order |
Yes |
Yes |
Yes |
Yes |
Yes |
frequency of inspection |
once a month |
once every six months |
none required |
none required |
once a month |
who performs inspection |
certificate of fitness holder3 |
(for systems with 30 heads or less) N/A |
N/A |
certificate of fitness holder |
scope of inspection |
connections, if any are ready for immediate use sealed in open position prescribed by the Fire Commisioner connections, if any are ready for immediate use sealed in open position prescribed by the Fire Commisioner N/A |
N/A |
connections, if any are ready for immediate use detailed record of inspections |
must be kept and available to the Fire Department Yes |
Yes |
N/A |
N/A |
Yes |
supply of 6 replacement |
heads at premises 4 Yes |
Yes |
No |
No |
Yes |
employee must be instructed in |
location and status of system control valves Yes |
Yes |
No |
No |
Yes |
|
|---|
| Related Tests | J-2 FOUR UNITS OR MORE | J-2 FOUR UNITS OR MORE (In a building 6 stries or 75 ft. in height or less with a secondary means of egress from all units and occupiable spaces) | J-2 THREE UNITS OR LESS | J-3 | ALL OTHER OCCUPANCIES
| every 30 months a flow test must be |
performed by a licensed plumber or a licensed fire suppression contractor, certified on Fire Department forms and kept for at least 5 years Yes |
Yes |
No |
No |
No |
every 5 years, in the presence of a |
Fire Department representative, a hydrostatic pressure test of any Fire Department connections to sprinkler and/or standpipe system Yes |
Yes |
No |
No |
Yes |
Yes |
Yes |
No |
No |
Yes |
Yes |
Yes |
No |
No |
No |
Yes |
Yes |
No |
No |
No |
|
|---|
______________________________________________1 This table is a summary. Refer to Local LAw 10/99 (Administrative Code Section 27-4265) for full text 2 This table concerns Fire Department requirements. Section 27-2050 of the Administrative Code (Housing Maintenance Code) provides inspection requirements for sprinklers in converted dwelling units and in tenements used for single room occupancies. 3 Issued by the Fire Department 4 Only 3 heads are required for systems pursuant to RS 17-2A 5 See section 27-4265 (d) & (e) which require, among other things, that standpipe and sprinkler pumps be ooperatedat least once every 30 days to subject the system to a hydrostatic pressure of at least 50 lbs. per sq. inch, that any structure with a required standpipe have a qualified person in charge of the system, that such qualified operators be available (depending upon the capacity of the system or building use) |
| Prepared by: The Pumbing Foundation City of New York/Mechanical Contractors Association of New York, Inc. (06/99) |